Diverted Neutral Current Demonstration - Normal, Open CNE, Current Circulation (Part 2)
A demonstration of diverted neutral current using a 12V AC test rig. This represents two adjacent properties with TN-C-S supplies via a CNE (combined neutral and earth) cable and a shared extraneous conductive part.
Demonstration includes:
► normal operation
► current sharing between the CNE and bonding conductors
► what happens with an open CNE in one property and not in the adjacent one
► the situation with more than two properties all connected to the same extraneous part.
In all cases, current can be found in the bonding conductors connected to shared metallic parts such as gas or water pipes.
Note that this demonstration uses a custom manufactured test rig which runs on an isolated 12 volt AC supply. Some of the items shown would be dangerous if done with 230V or a real electrical installation.
Переглядів: 68 455

Відео

Diverted Neutral Current - Description Overview Part 1
Переглядів 26 тис.9 місяців тому
Diverted Neutral Current, also known as Neutral Current Diversion. This can occur both in normal operation and when there is a problem with the supply network. Part 1 covers the basic principles of both.
Extension Lead Repair - MK Panel Sockets
Переглядів 11 тис.10 місяців тому
Replacing panel mounted MK sockets in a metal extension reel. Sockets are MK 735WHI, and are the same size as those made decades ago. There is an ancient data sheet for the original ones here: docs.rs-online.com/739a/0900766b811ef79c.pdf which is dated July 1959. Flex is 2.5mm² 3 core PVC. This is significantly larger than most extension reels available today which are typically 1.5mm² or even ...
Wylex Mini Consumer Unit, RCBO and SPD
Переглядів 19 тис.10 місяців тому
A Wylex metal 2 way consumer unit, 40A Type A RCBO with switched neutral, and a Type 2 surge protection device. This one will be used for an EVSE installation, but it could be used for other situations where a new circuit is required. Box with main switch: NM206/63 Surge protection device: NMT2SPD3W/1 40A compact RCBO with switched neutral: NHXS1B40 Patreon: www.patreon.com/jwflame Ko-Fi: ko-fi...
Electric Vehicle Charging - Connectors, AC / DC, Home or Away
Переглядів 20 тис.11 місяців тому
Charging electric vehicles using AC or DC, and the Type 2 connector which is found on most recent electric vehicles in the UK and most of the world. Also covers older vehicles with Type 1 and CHAdeMO connectors, and the situation with Tesla vehicles and charging. Most of this does not apply to the USA, where Type 1 and Type 1 CCS is common for existing non-Tesla vehicles and Tesla has it's own ...
Power and Energy Monitor Plug
Переглядів 11 тис.11 місяців тому
A typical power and energy monitor that can be used with any plug in appliance. The main features are kWh and elapsed time. Also shows voltage, current, watts, VA and power factor. Patreon: www.patreon.com/jwflame Ko-Fi: ko-fi.com/jwflame Website: flameport.com/
Power and Energy - Watts vs Watt Hours, Energy Cost and Battery Capacity
Переглядів 22 тис.Рік тому
Watts vs Watt Hours Amp Hours to Watt Hours Power is the rate at which electricity is used, energy is the total amount used over a certain period of time. Includes example calculations for the total energy and cost used, and the capacity of batteries.
Types Of RCD
Переглядів 58 тис.Рік тому
Types of Residual Current Devices, Type AC, A, F, B and B . What each type is intended for and what fault currents they will work with. Effective September 2022, BS7671 requires a minimum of Type A for the majority of installations. However some devices are not suitable for use with Type A and require others such as Type F or B.
BS7671 18th Edition Amendment 2 Appendices
Переглядів 8 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. The final episode in this series covers the changes in the 18th edition Amendment 2 appendices. IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPal Donatio...
BS7671 18th Edition Amendment 2 Part 8
Переглядів 8 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. This is a summary of the main concepts in the new Part 8, Prosumers Electrical Installations. IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPal Donations...
BS7671 18th Edition Amendment 2 Part 7
Переглядів 6 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. This covers some of the changes in part 7. IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPal Donations: xo4.uk/?PPP ► Social Media: Twitter: ...
BS7671 18th Edition Amendment 2 Part 6
Переглядів 6 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. This covers the main changes in part 6. Model forms download: electrical.theiet.org/bs-7671/model-forms/ IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPa...
BS7671 18th Edition Amendment 2 Part 5
Переглядів 8 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. This covers the main changes in part 5. IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPal Donations: xo4.uk/?PPP ► Social Media: Twitter: jwf...
BS7671 18th Edition Amendment 2 Part 4
Переглядів 11 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. This covers the main changes in part 4. IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPal Donations: xo4.uk/?PPP ► Social Media: Twitter: jwf...
BS7671 18th Edition Amendment 2 Parts 1-3
Переглядів 27 тис.2 роки тому
BS7671 18th Amendment 2, published March 2022. This covers the main changes in part 1, 2 and 3. Electropedia website: www.electropedia.org/ IET Fake Awareness with list of approved suppliers: electrical.theiet.org/bs-7671/fake-awareness/ Other videos in this series: ua-cam.com/play/PLVsHvs2SuqmqMoXZCFp_CYTgZH_Y2ywwk.html ► Support this channel: Patreon: www.patreon.com/jwflame PayPal Donations:...
Driving Electric Vehicles - Not much different to any other car or van
Переглядів 17 тис.2 роки тому
Driving Electric Vehicles - Not much different to any other car or van
TT Installations
Переглядів 56 тис.2 роки тому
TT Installations
Racal-Guardall 1980s PIR Sensor Teardown - Compared with Modern Equivalent
Переглядів 11 тис.2 роки тому
Racal-Guardall 1980s PIR Sensor Teardown - Compared with Modern Equivalent
ConduDisc Final Tests - 4 Months Later
Переглядів 17 тис.2 роки тому
ConduDisc Final Tests - 4 Months Later
Smoke Alarm Wiring Fail
Переглядів 49 тис.2 роки тому
Smoke Alarm Wiring Fail
SY Cable is Not Armoured, Not for Outside Use
Переглядів 40 тис.2 роки тому
SY Cable is Not Armoured, Not for Outside Use
Siemens VOELCB examination and Tinned Copper or Aluminium wiring?
Переглядів 12 тис.2 роки тому
Siemens VOELCB examination and Tinned Copper or Aluminium wiring?
Octopus Box by Hartley Electromotives Limited 1958
Переглядів 25 тис.2 роки тому
Octopus Box by Hartley Electromotives Limited 1958
Screws - Phillips or Pozidriv ?
Переглядів 127 тис.3 роки тому
Screws - Phillips or Pozidriv ?
Led Tape Part 2
Переглядів 12 тис.3 роки тому
Led Tape Part 2
Circuit Breakers Prague 1983
Переглядів 12 тис.3 роки тому
Circuit Breakers Prague 1983
LED Tape Part 1
Переглядів 19 тис.3 роки тому
LED Tape Part 1
ConduDisc and Conducrete Installation
Переглядів 17 тис.3 роки тому
ConduDisc and Conducrete Installation
Pepperpot Fuses, Switch and Meter Card
Переглядів 12 тис.3 роки тому
Pepperpot Fuses, Switch and Meter Card
Federal Electric Circuit Breakers
Переглядів 11 тис.3 роки тому
Federal Electric Circuit Breakers

КОМЕНТАРІ

  • @benrichards1
    @benrichards1 21 годину тому

    How that essentials light switch got through design is beyond me. What a ridiculous product! Wont even fit (properly) in a 25mm back box. Someone needs sacking! The mind boggles.

  • @peterjones2761
    @peterjones2761 День тому

    Im wondering which direction you would go away from the original earth stake. If i had a new overhead pole put in for my new supply (I'm very out in the sticks) would I be advised to head towards the pole which happens to be in the same direction of an overhead transformer for me and a neighbour on the next farm. The new supply is PME but the estimator guy said to put an earth stake in with a 25mm CPC connection to it. Never had that request before in my youger days of new house etc.

  • @leeyo5494
    @leeyo5494 День тому

    HELLO, how many double sockets can i fit on a 2.5 cable radial, thanks

  • @Dog-whisperer7494
    @Dog-whisperer7494 2 дні тому

    John can you explain why you used the resistance calculating how much current was used . 2300w / 230v = 10amp but going by the resistance it’s 9.58 amps . Please explain .

  • @paultutton9443
    @paultutton9443 2 дні тому

    I hope that all's well John. Having learned so much from your UA-cam content I have my fingers crossed that it won't be too long before we hear from you again - your clear explanations and dry humour are much missed! Best wishes from just down the road in Dorchester.

  • @johnpaulirvine5845
    @johnpaulirvine5845 2 дні тому

    Brilliant, John, but also quite scary... what would be the answer, then, if you're wiring up some external containers to a PME supply? Put in an earth stake? Thanks.

  • @JohnJKelly-of4dc
    @JohnJKelly-of4dc 2 дні тому

    Every house i wired, always drove earth rods. 3 core going out to the cutout, and youd be connected into the earth block, which is basically the neutral block there. Theres an inspection box for the earth rod, which is normally placed under the meter cabinet externally.

  • @user-kk8fk3sb4k
    @user-kk8fk3sb4k 4 дні тому

    Someone playing with my socket I can hear the cracking when I am in my room most times

  • @boosterhuiz2779
    @boosterhuiz2779 5 днів тому

    It just shows how casual people are. 500 volts? Your hand was millimetres away from it. I would want at least 500mm distance

    • @jwflame
      @jwflame 2 дні тому

      Current from that and similar test devices is limited to 1mA, far too little to cause any injury.

  • @eishwezin3029
    @eishwezin3029 5 днів тому

    Thank you Sir.

  • @andrewforsyth4799
    @andrewforsyth4799 6 днів тому

    Think i got it second time round was looking at ring ,,thanks

  • @andrewforsyth4799
    @andrewforsyth4799 6 днів тому

    Hi j, really like your channel its very informative, just come across this older vidio of yours which i do remember, could you explain how the newer iet brown book now reference's this same model regarding the 3036 fuse . They've changed the book because of your teaching ,,brill!!

  • @MeGrahamPage
    @MeGrahamPage 6 днів тому

    If you are in a shower area my existing pull cord switches a fan, Light and shower pump from the same switch. Is a special load carry switch necessary if you fitted juts outside shower room door? Will they carry the load? Should a relay be employed though; it still has to take a load ...so i am confused? yes your videos are a carming releaf from a importand but dry subject...thanks.

  • @gerryboy458
    @gerryboy458 8 днів тому

    Very good way of explaining this.

  • @SPDTDL
    @SPDTDL 9 днів тому

    Afternoon JW. Just purchased a 4 year old new build. It has an EV charger installed using 2.5mm T&A, with a 25A MCB on the consumer unit. Charger has been capped to 25A using dip switches inside the unit. When I plug my car in, as expected it’s capped at 25A which is fast enough for me. Is this OK or should I be expecting a house fire? 😅

    • @jwflame
      @jwflame 8 днів тому

      May be acceptable, if the cable is either surface clipped or direct in the plaster/masonry. Not acceptable if it's in any kind of conduit or ducting, or passes through insulation. Even if it is surface clipped, it will get fairly warm in use, as it will be used pretty much at it's maximum rating.

    • @SPDTDL
      @SPDTDL 7 днів тому

      @@jwflame Thank you JW. I managed to find out it’s 'clipped direct'. However, below the consumer unit is a switch that enables me to turn the EV charger on and off. 20A Double Pole switch. I assume this would not be a good thing having 25A passed through it?

  • @ndear2955
    @ndear2955 9 днів тому

    Wow what a stupid design, thanks for sharing!

  • @Webbster77
    @Webbster77 9 днів тому

    John, so if I have a steel frame pergola in a garden that has lights and heaters attached and wired through the frame it would need bonding accordingly as well then?

  • @mickeyfletcher9292
    @mickeyfletcher9292 9 днів тому

    Can you fit a rcbo in a panel protected by a RCD?

    • @jwflame
      @jwflame 9 днів тому

      Only if the RCBO can be connected directly to the main switch, and not via the RCD.

  • @majorredbeard
    @majorredbeard 10 днів тому

    Excellent description and thanks for the practical way of telling between them.

  • @chrisrhodes1127
    @chrisrhodes1127 10 днів тому

    Diversity Perfectly explained !

  • @jakobrebeki
    @jakobrebeki 10 днів тому

    Dear John, have you quit doing UA-cam videos....

    • @jwflame
      @jwflame 10 днів тому

      No, there will be more at some point.

  • @marklittler784
    @marklittler784 11 днів тому

    Like going back to school 😊

  • @geniusmarcsays2434
    @geniusmarcsays2434 11 днів тому

    he did not explain how he connected the wires...i mean what i see is a plug with the 2 wires touching, that's a short circuit

    • @jwflame
      @jwflame 9 днів тому

      It's a demonstration of the AFDDs. The wiring is not relevant, and isn't what would normally be used because it's just a demonstration.

    • @geniusmarcsays2434
      @geniusmarcsays2434 9 днів тому

      @@jwflame yes, but i still want to know how you tripped the circuit.. did you make arc flash on a parallelle circuit?

  • @craiginboro679
    @craiginboro679 13 днів тому

    The lighting circuit isn't RADIAL, they used to be. The lighting circuit is a Ring, you actually drew a ring circuit, ie the main conductor left the consumer unit and returned to it. A radial is where power is supplied to each device and doesn't have a return. Ps blue=black, brown=red. Unfortunately electricians use a red switch wire to connect to live. If they used a black switch wire to connect to the 'ring' live it would be obvious it was a switch wire. No extra bits of sheathing required.

    • @jwflame
      @jwflame 9 днів тому

      No idea which video you watched, but it certainly wasn't this one.

  • @georgedavall9449
    @georgedavall9449 14 днів тому

    J.W. !!!!!!!!!!!!!!!!! Crackin video mate, but slow down and enunciate a little clearer, Sir, Thank You 🙄

  • @tobybutler9493
    @tobybutler9493 14 днів тому

    Great video - clear and useful. Thx

  • @fredbettesworth5397
    @fredbettesworth5397 16 днів тому

    ill have crabbtree dist boargs on site. Looking for blanking plates

  • @aminabbasipiani9131
    @aminabbasipiani9131 16 днів тому

    hi guys, i have a question. how does SPD protect your electrical appliances? when a high voltage occurs and SPD detects it, will your circuits be isolated?

    • @jwflame
      @jwflame 9 днів тому

      The SPD becomes a short circuit for the duration of the overvoltage, so the voltage is reduced and the energy ends up as heat in the SPD. Nothing is isolated.

  • @ifell3
    @ifell3 17 днів тому

    Hi John, looking at your inverter it has a grounding stud, is this a ground for the DC then? Kind regards

  • @alasdairmunro1953
    @alasdairmunro1953 17 днів тому

    Pulled a few of those in my time as a firefighter, to isolate supply when BA crews are searching in a building.

  • @matthewhammond859
    @matthewhammond859 17 днів тому

    Are the building regs statutory or not?

    • @jwflame
      @jwflame 16 днів тому

      They are. www.legislation.gov.uk/uksi/2010/2214/contents

    • @matthewhammond859
      @matthewhammond859 16 днів тому

      @@jwflame Thanks

  • @jorgecastro199
    @jorgecastro199 17 днів тому

    Hi, good job, can you tell me were i can get new brushes? Thank you.

  • @ross9580
    @ross9580 17 днів тому

    Is the Americium a solid or an encapsulated powder? Any risk of a powerful compressed airblast accidentally dispersing it?

  • @digitraxuk
    @digitraxuk 18 днів тому

    Thank you John for another very clearly presented topic. With a TT system in the main house would it only be beneficial to connect the 10mm 3core SWA cable (cpc) to the outbuilding (with water and gas services) consumer unit MET where it has its own separate earth rod. I would imagine this setup, rather than keeping the two completely separate as you presented, is beneficial in trying to keep the Ra to a minimum. Or is it a pointlessly small benefit since you are relying on RCD for earth fault protection? I hope that makes sense? Many thanks for my crazy brain working overtime.

  • @scampbell8136
    @scampbell8136 19 днів тому

    all my questions answered in ne video, great thank you .

  • @Rineality
    @Rineality 19 днів тому

    Don't be afraid john

  • @afzaalawan
    @afzaalawan 20 днів тому

    extreemly long video for a simple concept

  • @elmarbayramov9312
    @elmarbayramov9312 20 днів тому

    What is the significance of the different colors of the clades?

  • @eazyrat
    @eazyrat 20 днів тому

    Thanks. I tried these tests got 50 ohms on one reading. The problem for me wasn't that the heater wasn't working but the reset kept activating. The water did seem very hot. Broken stat?

  • @GrahamBurton-wx4jd
    @GrahamBurton-wx4jd 20 днів тому

    hi john -thanks for explaining how this valve actually works -one question -will the valve move independenly of other contacts -ie will the valve still move from say the heating only position to the hot water only position even if the hot water thermostat is not calling for additional heat or will it stay in the hot water only position until the thermostat contact is triggered-best regatds graham

  • @awinbisa
    @awinbisa 20 днів тому

    Thanks for your amazing videos. Did you ever consider reading the shipping forecast? I love your style.

  • @tonyevic
    @tonyevic 20 днів тому

    and what is the point of terminating an earth to that fitting….? ( apart from the ‘regs’ say so!)

  • @train4905
    @train4905 21 день тому

    Awsome john thankyou😊😊

  • @user-ho7ez6xm3s
    @user-ho7ez6xm3s 21 день тому

    Thank you sir.

  • @deanesau9106
    @deanesau9106 22 дні тому

    John - Top G

  • @danstark462
    @danstark462 22 дні тому

    John i haven't had the pleasure to see all your vids. I was wondering if you could post or repost a vid on you fixing a 12v car battery charger or a 120v electric farm fencer. Thanks. Your vids are interesting i enjoy them.

  • @lrdisco2005
    @lrdisco2005 23 дні тому

    Excellent explanation from real world experience.

  • @altvamp
    @altvamp 23 дні тому

    It's got the right brand name, it might make you see stars! Wouldn't pass UK safety regulations.

  • @Trafficlight678
    @Trafficlight678 23 дні тому

    In the USA we use Edison type lamp holders rather than bayonets. The Edison lamps use a screw thread system instead of push and twist

  • @Trafficlight678
    @Trafficlight678 23 дні тому

    I am living in the USA and we measure cord thickness in the form of gauge rather than millimeter. In the USA the thickness of the flex would be 14 gauge which in the UK is 1 millimeter